The 680 communicates with Building Automation Systems using BACnet® or Modbus® for alert notification, remote monitoring and adjustment capability. It uses a tekmar Snow/Ice Sensor 090 or a Snow Sensor 095 to automatically detect snow or ice on the snow melting slab. Up to two snow/ice sensors can be installed, thereby increasing detection area and providing backup redundancy in the case of sensor failure. Upon detection of snow or ice, the 680 operates an electric heating cable, a single hydronic condensing or non-condensing boiler, or a steam valve to provide heat to the snow melt load. The 680 provides boiler return protection by operating a mixing valve or variable speed injection mixing. Monitoring of energy consumption is possible when it is connected to an optional flow sensor.
Features
- Automatic snow/ice detection
- BACnet or Modbus communication
- Cold weather cut off
- EconoMelt
- Energy monitoring
- Exercising
- Idling
- Slab protection
- Storm
- Supports both inslab & retrofit aerial sensors
- Tandem snow/ice detection
- Warm weather shut down
Technical
680 Installation & Operation
680 Submittal
680 BAS Integration Manual
Product Website
Specifications
Control |
Microprocessor control. This is not a safety (limit) control. |
Packaged weight |
6.5 lb. (2950 g) |
Dimensions |
8-1/16″ H x 11-1/8″ W x 2-15/16″ D (204 x 282 x 74 mm) |
Display |
3-1/4″ color touchscreen, 320 x 205 pixels |
Enclosure |
PC+ABS plastic with steel conduit connection walls, NEMA type 1 |
Approvals |
CSA C US, meets class B: ICES & FCC Part 15, BTL Listed |
Ambient conditions |
Indoor use only, 32 to 122°F (0 to 50°C), < 90% RH non-condensing |
Power supply |
115 V (ac) ± 10%, 60 Hz, 43 VA standby, 320 VA max |
Primary, system pump relays |
230 V (ac), 10 A, 1/2 hp |
Boiler pump relay |
230 V (ac), 5 A, 1/3 hp |
Boiler stage relays |
230 V (ac), 5 A |
Boiler modulation output |
0-10 V (dc) 500 Ω min impedance / 4-20 mA 1 kΩ max impedance |
Injection mixing pump |
230 V (ac), 2.4 A |
Floating mixing output |
230 V (ac), 5 A |
Analog mixing output |
0-10 V (dc) 500 Ω min impedance / 4-20 mA 1 kΩ max impedance |
Flow sensor |
4-20 mA, 20 V (dc) power supply by control |
Pressure sensor |
0.5 – 4.5 V (dc) ratiometric, 10kΩ min load, 5 V (dc) power supply by control |
Communications |
BACnet IP, BACnet MSTP, Modbus MSTP |
Sensors |
NTC thermistor, 10 kΩ @ 77°F (25°C ± 0.2°C) =3892 |
-Included |
Outdoor Sensor 070 and 3 of Universal Sensor 082 |
-Optional |
tekmar type: 072, 073, 082, 090, 094, 095 |
Warranty |
Limited 3 Year Warranty |